General Information
Application | DC Circuit SPD |
Installation Method | Fig. A – Parallel or Modified-Series |
Technology | Fig. B – Metal Oxide Varistor (MOV) |
Protection Modes | (+) to (-); (+) to (G); (-) to (G) |
Modular | Yes |
Agency | UL1449 Recognized Type 4CA |
Warranty | 2 Years |
Electrical Information
Nominal Voltage | 12Vdc |
Max. Operating Voltage (MCOV) | 24V |
Maximum Surge Current | 20kA |
Max. Line Current (OCPD Size) | 20A |
Nom. Discharge Current (In) | 10kA |
Operating Temperature | -40°C to 85°C |
Form C Contact | Fig. D – 250Vac / .5a Max (30Vdc / 3a Max) |
Mechanical Information
Termination Method | Screw Terminals: (+) & (-) (#8 – #14AWG); Ground (#4 – #12AWG) |
Disconnect Indication | Visual Indication & Form C Contact |
Housing | Thermoplastic NEMA 2 (IP20) |
Dimensions | Fig. C – .71″W x 3.54″D x 2.64″H |
Mounting | 35mm Symmetrical DIN Rail |
Outdoor Use | No |
ROHs Compliant | Yes |