Series TSr (Modular)

  • NEMA 4X Fiberglass Enclosure
  • Individual, Replaceable Modules
  • 50 – 300kA per Mode Models
  • TSrc Commercial Series (TpMOV & Filter Capacitors)
  • TSri Industrial Series (adds Silicon Avalanche Diodes)
  • Optional Surge Counter/Audible Alarm
  • Optional Form C Contactand/or Phase Loss Contact
  • Optional Extended Filter Network (EFN)
  • Optional Multi-Function Relay (MFR)
  • UL1449 5th Edition / UL1283 7th Edition Listed

Downloads


Need help configuring models and options?

Give us a call 804-355-1100

Design

Low Impedance Surge Paths

  • Yellow zinc plated, low carbon steel back pan
  • ¼” thick x ½” wide C11000 Copper Bus Bar
  • #6AWG, Rope-Lay internal Power Wiring

Replaceable Modules

  • Individual, Replaceable Module
  • Secures to Buss Bars with ¼” hardware
  • LED indication on Each Module

Hybrid Suppression Technology

  • TSrc (Commercial Series) – 2-Tier Design
  • TSri (Industrial Series) – 3-Tier Design

Surge Component Technology

 ?

Thermally Protected, Metal Oxide Varistor (TpMOV)

  • ANSI/UL 1449 4th Edition, Type 1 Component
  • Fail-Safe Design
  • 50kA 8x20us Rated
  • Visual Fail indicator as well as a normally open micro-switch
  • Applied L-N, L-G & N-G

EMI / RFI Filter Capacitors

  • X2 SMPS EMI Suppression Capacitors
  • 1uf, 305Vac Rated
  • Applied L-N &/or L-G

TVS Diodes / Silicone Avalanche Diodes (SADs)

  • UL 497B Recognized
  • Provide Faster Response Time
  • 1.5kW or 15kW Sizes

Input Termination

 ?

Terminal Blocks (Standard)

Slotted Screw Terminal Blocks that accept up to a #4AWG. Copper Conductor

Distribution Blocks (Optional)

Slotted Screw Terminal Blocks that accept up to a #2AWG. Copper Conductor

Fused Disconnect (Optional)

Integral, Fused Disconnected Switch that accept up to a #4AWG. Copper Conductor

Monitoring

 ?

Form C “Dry” Contacts (Standard)

  • Every TSr comes standard with (2) Form C, “Dry” Contacts that change state on an SPD Module failure
  • Optional Phase Loss “Dry” Contacts available that changes state on any loss of phase

MODULE LEDs (Standard on all TSr’s)

  • Each Suppression Module contains a Green (Module Good) and Red (Module Failed) LED
  • Each Module is Keyed & color coded to prevent installing a wrong replaceable module
  • ¼-20 Serrated Hex Nuts secures Module in Place
  • Each Module wired back to Power Supply for Status control

SURGE COUNTER and/or AUDIBLE ALARM (Optional)

  • Module LEDs & Dual Form C Contacts, PLUS;
  • Audible Alarm with Silence Button;
  • Surge Counter with (8) sensitivity settings;
  • Status LED’s
  • Monitor Power On / Off Button
  • Horn Disable option

Additional Options

EXTENDED FILTER NETWORK (Optional)

Provides additional EMI/RFI electrical noise attenuation up to 53dB in the range of 50kHz to 100MHz as defined by MIL-STD-220A test procedures.

MULTI-FUNCTION RELAY (Optional)

Provides Output Contact for status of Over / Under Voltage within a Range, Phase Loss, Phase Rotation & Phase Balance

POWER QUALITY MONITOR (Optional)

  • Total Harmonics Distortion (THD)
  • Waveform Capture
  • Onboard Ethernet
  • Data & Event Logging
  • Current Transformers
  • [Optional] Environmental Monitoring

Enclosures

FIBERGLASS ENCLOSURE (Standard)

  • Made from hot compression molded halogen free, self extinguishing fiberglass reinforced polyester (FRP)
  • 1/4” transparent Lexan™ window
  • Protection Rating: NEMA Type 3; NEMA Type 3R; NEMA Type 4; NEMA Type 4X; NEMA Type 12; NEMA Type 13; IP66 16” H x 14” W x 8” D
    or 18” H x 16” W x 10” D

STAINLESS STEEL ENCLOSURE (Optional)

  • Type 304 Stainless Steel with #4 Brushed Finish
  • Protection Rating: NEMA Type 3; NEMA Type 3R; NEMA Type 4; NEMA Type 4X; NEMA Type 12; NEMA Type 13; IP66 20” H x 16” W x 8” D

POWER QUALITY MONITOR SYSTEM (Optional)

  • Incorporates (2) Fiberglass enclosures on a stainless steel back pan
  • Protection Rating: NEMA Type 3; NEMA Type 3R; NEMA Type 4; NEMA Type 4X; NEMA Type 12; NEMA Type 13; IP66 48” H x 24” W x 8.50” D