General Specifications
| Application | 1-Pair (2W + Shield) Data Line |
| Installation Method | Fig. A – Series |
| Technology | Fig. B – Gas Tube & TVS Diode |
| Protection Modes | Line-Ground & Shield-Ground |
| Serviceability | Modular |
| Agency | UL 497B |
| Warranty | 2 Years |
Electrical Specifications
| Nominal Voltage | 5V |
| Max. Continuous Operating Voltage (MCOV) | 8V |
| Max. Line Current | 300mA |
| Maximum Surge Current | 20kA |
| Maximim Frequency | 3MHz |
| Insertion Loss | > 1dB |
| Maximum Data Rate | 10/100bps |
| Ambient Temp | -50°C to 85°C |
Mechanical Specifications
| Termination Method | Screw Terminals (#12-20AWG) |
| Disconnect Indication | Transmission Interruption |
| Housing | NEMA 2 (IP20) / UL94-V0 Thermoplastic |
| Dimensions | Fig. C – .51″W x 3.54″D x 2.56″H |
| Mounting | 35mm Symmetrical DIN Rail |
| Install Location | Indoor |
| Environmental | ROHS |